Transformer Fundamentals
The ideal transformer is a ratio: volts scale by the turns, amps by the inverse, and impedance by the square. The real machine adds a series impedance and two loss mechanisms — and that one nameplate number, %Z, ends up setting both how far the voltage droops under load and how hard the secondary can hit a bolted fault. Load the transformer below and watch regulation, efficiency, and fault duty move together.
13 800 Δ — 480Y/277 V · 60 Hz
a = N₁/N₂ = 28.75
Core loss burns whenever the primary is energized — load or no load. Copper loss is I²R and grows with the square of load.
Approximate equivalent circuit in per-unit. The shunt branch models the core — Rc carries the no-load loss, jXm the magnetizing current — and the series R + jX is the nameplate %Z split by the X/R ratio (colored to match the drop vectors in the phasor diagram). The ideal 28.75 : 1 transformer on the right is pure ratio arithmetic.
VR (received voltage) is the reference. The I·R and j·I·X drop vectors are drawn ×5 actual size so the drop triangle is visible — real drops are only a few percent of V.
The ideal transformer is pure ratio arithmetic. With a = N₁/N₂ turns, voltage scales down by a, current scales up by a, and an impedance seen through the transformer scales by a²:
The real machine adds a series impedance — winding resistance plus leakage reactance — quoted on the nameplate as %Z (the voltage needed to push rated current through a shorted secondary). Split it with the X/R ratio: R = Z·cos θZ, X = Z·sin θZ. Load current through that impedance is what makes the secondary voltage move:
With lagging current the I·X drop lines up with the voltage and the secondary droops. With leading current the reactive drop reverses and the secondary can rise above its no-load value — negative regulation, the same mechanism as Ferranti rise on a lightly-loaded cable.
Losses live in two places. Hysteresis and eddy currents in the core steel cost a fixed Pfe from the moment the primary is energized; I²R heating in the copper costs Pcu ∝ load². Efficiency peaks exactly where the two are equal:
%Z is the designer's tradeoff. The same impedance that softens the voltage under load is all that limits a bolted secondary fault (with a stiff primary source):